NEC Commercial Electrical Engineering
Three-Phase Transformer KVA & Ampacity Sizer
Calculate transformer standard KVA ratings (15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA), 480V primary Full Load Amps (FLA), and 208Y/120V secondary distribution breaker sizing.
Electrical Load & Voltage Configuration
KVA Sizing & Ampacity Takeoff
Standard Transformer Size
NEMA standard dry-type KVA rating
Primary Full Load Amps (480V)
FLA = (KVA * 1000) / (1.732 * 480)
Secondary Full Load Amps (208V)
FLA = (KVA * 1000) / (1.732 * 208)
NEC Article 450 requires overcurrent protection for transformers. A 112.5 KVA 480V unit typically uses a 150A primary breaker (125% rating) and 400A secondary main breaker.