NEC National Electrical Code (Article 680)

Hot Tub Wire Gauge & Breaker Sizer

Ensure code compliance and fire safety for 240V spa installations. Calculate circuit breaker amps, copper THHN/Romex wire gauge, and voltage drop across long runs.

Electrical Parameters

NEC Code Requirements

Copper Wire Size 6 AWG Hot & Neutral
Ground Wire 8 AWG Insulated green
GFCI Subpanel 50A GFCI Outdoor disconnect
Conduit Size 1" PVC Schedule 40/80
Voltage Drop 1.2% < 3% safe NEC
Est Material BOM $485 Wire + subpanel
Required Disconnect Distance: Min 5 ft, Max 50 ft (Line of Sight)
Trench Burial Depth: 18" in PVC / 24" Direct Burial